Bộ cách ly tín hiệu MTL4514
Thông số kỹ thuật bộ cách ly tín hiệu MTL MTL4514
đại lý mtl | đại lý MTL4514
nhà phân phối mtl | nhà phân phối MTL4514
-
Nhà cung cấp MTL Instruments Việt Nam : Usually ships in 1 – 10 .
-
Nhà sản xuất: MTL Instruments
-
MTL4514
-
MTL4514/B
-
SWITCH/ PROXIMITY DETECTOR INTERFACE
-
1-channel, line fault detection, phase reversal
-
The MTL4514 enables a safe area load to be controlled, through a relay, by a proximity detector or switch located in a hazardous area.
-
Number of channels: One
Location of switch: Zone 0, IIC, T6 hazardous area / Div.1, Group A, hazardous location
Location of proximity detector: Zone 0, IIC, T4 6 hazardous area, if suitably certified/ Div.1, Group A, hazardous location
Hazardous area inputs
Inputs conforming to BS EN60947 5 6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor: 7 to 9V dc from 1k? ±10% -
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2k? in input circuit)
Outputs open if input < 1.2mA (> 10k? in input circuit)
Hysteresis: 200µA (650?) nominal -
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults
are indicated by an LED. Line fault relay is energised and channel
output relay de-energised if input line-fault detected
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100?
Short-circuit alarm off if Rin > 360? -
Note: Resistors must be fitted when using the LFD facility with a contact input
500? to 1k? in series with switch
20k? to 25k? in parallel with switch -
Safe-area output
Channel: Single pole relay with changeover contacts
LFD: Single pole relay with changeover contacts -
Khối lượng đóng gói : 1 Kg